E3 DTS (Distributed Temperature Sensing)

F7 System Customer Review

Customer Reviews

Real-time Monitoring

Proactive Safety Alerts

Operational Continuity

Customer Case

Trust Indicators

Product Functions

Comprehensive Temperature Alert Strategies

Supports fixed-temperature, rate-of-rise, and differential temperature alarms to meet diverse application requirements, with a detection range of 40 ℃ to 120 ℃.

High-precision Temperature & Location Detection

Delivers temperature accuracy within ±0.5 ℃ and spatial resolution of ±0.5 m, enabling pinpoint thermal monitoring.

Long-range & Rapid Scanning

Covers up to 16 km per channel with a scanning cycle as fast as 1 second per channel, providing realtime, continuous temperature profiling.

One-click Fiber Fault Location

Automatically identifies attenuation points and evaluates loss for quick troubleshooting.

Flexible Zone Configuration

Allows custom zone division based on site layout, with electronic map display for clear status and alarm visualization.

BrowserBased Remote Monitoring

Built on a BS architecture; no client installation required—access and manage the system via any browser, supporting multidevice connectivity.

Product Parameters

Electronic Map

Supports electronic map display of zone status and alarm locations

Long Detection Range

Up to 16km per channel

High Measurement Accuracy

Measurement accuracy up to ±0.5°C

Flexible Zone Configuration

Zones can be arbitrarily divided according to the on-site environment

Number of Channels

Supports 2, 4, or 8 channels

RS485 Interface

2 ports: 1 for relay module expansion, 1 reserved for Modbus communication

Network Communication Interface

2 ports, 100M/10M auto-adaptation

Relay Interface

4 ports, normally open (NO) and common (COM)

USB Interface

2 ports

Power Supply Interface

DC24V, with overcurrent protection

Measurement Range

-40°C to 120°C

Maximum Measurement Distance

16km per channel

Spatial Resolution

±0.5 meters

Measurement Accuracy

±0.5°C

Minimum Measurement Cycle

1 second per channel